Measuring Voltage Drop

Voltage drop under typical operating conditions can easily be measured. If excessive voltage drop is suspected in a circuit, follow these steps:

Results
If a problem with the voltage exists at the main service - call the utility .

If voltage at main service was fine but low at service panel - check feeder from main service for problems.

If voltage at service panel was fine but low at outlet or controller, check branch circuit for problems.

Remember
A 480 volt circuit should be a minimum of 480 volts at the transformer secondary and a minimum of 440 at the equipment outlet or controller.

A 240 volt circuit should be a minimum of 240 volts at the transformer secondary and a minimum of 220 at the equipment outlet or controller.

A 120 volt circuit should be a minimum of 120 volts at the transformer secondary and a minimum of 110 at the equipment outlet or controller.